Typical Recharge Time: 8-12 Hours (90% of full capacity)
SYSTEM FEATURES:
LCD Indications: Input Voltage/Frequency, Output Voltage/Frequency, Battery Voltage, Load Watt/VA and %, Inverter Temperature, Operation Mode such as "On Line", "ON Batt" or On "Bypass", Fault Codes, Battery & Load Bar graph, Input Current, Output Current, Battery current
LED Indications: Normal Operation, Bypass, Abnormal, Fault and Battery Mode
Alarms/Protection: Batt. Low, DC High, Inverter Under/Over Voltage, UPS over Load, Short Circuit, Fan Failure and UPS fault, Transient surge, Input & Output Fuse
Overload Capability: 125% for 10 min, 125-150% for 1 min, 150% for 200ms
Transfer Time: AC to Battery: Oms, Inverter to Bypass: 4ms (Typical)
Dimensions (W x D x H) (mm): ( 144x400x215 A Net weight (kg) STANDARDS Quality Safety/ IP Rating 192x469x399 6 10.7 10.8 11.2 10.8 11.2 EMC/Performance COMMUNICATION INTERFACE Standard Optional ISO 9001:2015, ISO 140001:2015, BIS IEC/EN62040-1/IP20/Ip21 IEC/EN62040-2; IEC/EN62040-3, Complying to CE RS-232 SNMP/ModBus/Dry Contact/USB/RS-485 220x481x438